53
16.5.1. DISTRIBUTION FAN SPEEDS
Your furnace is equipped with a 4-speed blower. Using the central processing unit, we have created 6 functional
speeds. Refer to the following table
for the various speed configurations.
SPEED
CORRESPONDING DATA
CFM*
STATIC
PRESSURE
1
Blower speed #1 using 90V
900
0.2’’ W.C.
2
Blower speed #1 using 115V
1135
0.2’’ W.C.
3
Blower speed #2 using 98V
1400
0.2’’ W.C.
4
Blower speed #2 using 115V
1685
0.2’’ W.C.
5
Blower speed #3 using 115V
1790
0.2’’ W.C.
6
Blower speed #4 using 115V
1900
0.2’’ W.C.
*These results were measured at exit of plenum during laboratory tests. Results may vary depending of the
configuration and installation.
16.6. SYSTEM BALANCING
It is important to call upon a professional installer for the installation of the furnace and the ducting system
configuration. Certain check-ups must be performed and certain rules must be respected in order not to damage the
blower.
When all components are installed on the furnace and the ducting system is connected to the various rooms of the
house, you must balance the ducting system. In order to do so, start the distribution blower by going in the
‘’TROUBLESHOOT LINK’’ menu on Page 5 and select speed #4.
It is important to respect the velocity in the main duct, the secondary ducts, as well as the velocity at the room outlets.
The static pressure of your system must be adjusted to at least 0.2 IN.W.C. and must not exceed 0.5 IN.W.C. Finally,
make sure that you never exceed the maximum blower current.
16.7. OPERATING INSTRUCTIONS
16.7.1. HEAT Mode
When the temperature in your house is below the value at which your wall thermostat is programmed, a signal is sent
to your furnace through the PC board, activating the motorized damper located in front of the furnace and thus allowing
more oxygen to the fire. The RTD temperature probe, located inside the hot air plenum of your furnace, reads the
plenum temperature continuously. When the temperature reaches the start-up value selected by the user (KIP –
Kick-
in Point
), the distribution blower starts functioning at the minimum speed. Thereafter, the blower increments its speed
until it reaches the best efficiency point (BEP) determined by the manufacturer. If the temperature inside the hot air
plenum exceeds the limit determined by the manufacturer, the blower automatically selects the maximal speed and the
motorized damper closes in order to slow down combustion. When the temperature returns to a safe level, the blower
speed gradually returns to the speed required to maintain the BEP.
Summary of Contents for PF01015
Page 10: ...10 ADD ON WOOD ONLY WOOD ELECTRIC WOOD OIL ...
Page 13: ...13 INSTALLATION AND OPERATION INSTRUCTIONS CADDY ADD ON SERIAL INSTALLATION PF01015 ...
Page 16: ...16 Option 3 Option 4 ...
Page 17: ...17 EXAMPLE 1 EXAMPLE 2 ...
Page 63: ...63 20 GENERAL ELECTRICAL DIAGRAM STANDALONE FURNACE ...
Page 64: ...64 21 ELECTRICAL DIAGRAM FOR PARALLEL FURNACE ...
Page 65: ...65 22 ELECTRICAL DIAGRAM FOR ELECTRIC UNIT ...
Page 78: ...78 31 ELECTRICAL DIAGRAM BECKETT OIL UNIT ...
Page 79: ...79 32 ELECTRICAL DIAGRAM RIELLO OIL UNIT ...
Page 81: ...81 33 4 AIR CONDITIONNING DAMPER 33 5 HUMIDIFIER 33 6 HEAT PUMP ...
Page 82: ...82 34 EXPLODED VIEW AND PART LIST ...
Page 83: ...83 ...
Page 84: ...84 ...
Page 85: ...85 ...
Page 86: ...86 ...
Page 87: ...87 ...
Page 88: ...88 ...
Page 89: ...89 ...