14.7.4. FLOOR PROTECTION
If the floor is made of non-combustible material, no
floor protector is required.
If the floor is made of combustible material, a non-
combustible material floor protector is required (see
table below).
FLOOR PROTECTION*
CANADA
USA
A
18" (457 mm)
From door opening
16" (406 mm)
From door opening
B
N/A (USA only)
8" (203 mm)
From door opening
C
8" (203 mm)
N/A (Canada only)
D
8" (203 mm) – Note 1
N/A (Canada only)
E
N/A (USA only)
Note 2
*Steel with a minimum thickness of 0.015" (0.38 mm) or ceramic tiles sealed together with grout. No protection is required if the unit
is installed on a non-combustible floor (ex: concrete).
Note 1
: The floor protection at the back of the furnace is limited to the furnace’s required clearance (A) if such clearance is smaller
than 8 inches (203 mm).
Note 2
: Only required under the horizontal section of the connector. Must exceed each side of the connector pipe by at least 2
inches (51 mm).
Summary of Contents for PF01015
Page 10: ...10 ADD ON WOOD ONLY WOOD ELECTRIC WOOD OIL ...
Page 13: ...13 INSTALLATION AND OPERATION INSTRUCTIONS CADDY ADD ON SERIAL INSTALLATION PF01015 ...
Page 16: ...16 Option 3 Option 4 ...
Page 17: ...17 EXAMPLE 1 EXAMPLE 2 ...
Page 63: ...63 20 GENERAL ELECTRICAL DIAGRAM STANDALONE FURNACE ...
Page 64: ...64 21 ELECTRICAL DIAGRAM FOR PARALLEL FURNACE ...
Page 65: ...65 22 ELECTRICAL DIAGRAM FOR ELECTRIC UNIT ...
Page 78: ...78 31 ELECTRICAL DIAGRAM BECKETT OIL UNIT ...
Page 79: ...79 32 ELECTRICAL DIAGRAM RIELLO OIL UNIT ...
Page 81: ...81 33 4 AIR CONDITIONNING DAMPER 33 5 HUMIDIFIER 33 6 HEAT PUMP ...
Page 82: ...82 34 EXPLODED VIEW AND PART LIST ...
Page 83: ...83 ...
Page 84: ...84 ...
Page 85: ...85 ...
Page 86: ...86 ...
Page 87: ...87 ...
Page 88: ...88 ...
Page 89: ...89 ...