Maintenance and troubleshooting
Type 8792, 8793 REV.2
21.3.2 Error messages while running the
P.Q'LIN
function
Display
Causes of error
Remedy
TUNE
err/break
Manual termination of self-optimization
by pressing the
EXIT
key.
P.Q LIN
ERROR 1
No compressed air connected.
No change to process variable.
Connect compressed air.
Check process and, if required, switch on
pump or open the shut-off valve.
Check process sensor.
P.Q LIN
ERROR 2
Current node of the valve stroke was not
reached, as
•
Compressed air failure during
P.Q’LIN.
•
Autotune (
X.TUNE
) was not run.
Check compressed air supply.
Run Autotune (
X.TUNE
).
Table 67:
Error message for P.Q.‘LIN; process controller Type 8793
21.3.3 Error messages while the
P.TUNE
function is running
Display
Causes of error
Remedy
TUNE
err/break
Manual termination of self-optimization
by pressing the
EXIT
key.
P.TUNE
ERROR 1
No compressed air connected.
No change to process variable.
Connect compressed air.
Check process and, if required, switch on
pump or open the shut-off valve.
Check process sensor.
Table 68:
Error message for P.TUNE; process controller Type 8793
english