84
Basic setting of the process controller
Type 8792, 8793 REV.2
You have set the P.TUNE function.
To stop
P.TUNE
, press the left or right selection key
STOP
.
The changed data is saved in the memory (EEPROM) only when there is a switch to the process
level, by leaving the main menu (MAIN) using the left selection key
EXIT
.
Possible error messages when running
P.TUNE:
Display
Cause of error
Remedy
TUNE
err/break
Manual termination of self-optimization
by pressing the
EXIT
key.
P.TUNE
ERROR 1
No supply pressure connected.
Connect supply pressure.
No change to process variable.
Check process and, if required, switch
on pump or open the shut-off valve.
Check process sensor.
Table 33:
P.TUNE; possible error messages
After making all the settings described in chapter “Start-up”, the process controller is ready for operation.
Activation and configuration of auxiliary functions is described in the following chapter “26. Configuring the
auxiliary functions”.