180
Maintenance and troubleshooting
Type 8792, 8793 REV.2
21.4
Malfunctions
Problem
Possible causes
Remedy
POS
= 0 (when
CMD
> 0%) or
POS
= 100%, (when
CMD
< 100%).
PV
= 0 (when
SP
> 0) or
PV
=
PV
(when
SP
>
SP
).
Sealing function (
CUTOFF
) is
unintentionally activated.
Deactivate sealing
function.
Applies only to devices with
binary output:
Binary output does not switch.
Binary output:
•
Current > 100 mA
•
Short circuit
Check binary output
connection.
Applies only to devices with
process controller:
Device is not operating as a con-
troller, despite correctly imple-
mented settings.
P.CONTROL
menu option is in the main
menu. The device is therefore operating
as a process controller and expects
a process actual value at the corre-
sponding input.
Remove
P.CONTROL
menu option from the
main menu. See chapter
“19.1.2. Deactivating
auxiliary functions” on
page 228.
Table 71:
Other malfunctions
english