127
Auxiliary functions
Type 8792, 8793 REV.2
The status signals have different priorities.
If several diagnostic messages are available with different status signals, the status signal with the highest
priority is shown on the display.
Overview of the status signals according to NE 107 (NE = NAMUR recommendation):
Priority
1
2
3
4
Status signal
Meaning
Failure
Function check
Out of specification
Maintenance
required
Table 41:
CONFIG.MSG; overview of status signals
The following status signals have been preset at the factory for the messages of the diagnostic functions:
Diagnostic function
Status signal according to NE 107
Signal miniature
Priority
SERVICE.TIME
Maintenance required
4
TRAVEL.ACCU
Maintenance required
4
CYCLE.COUNTER
Maintenance required
4
TEMP.CHECK
Out of specification
3
STROKE.CHECK
Out of specification
3
PV.MONITOR
Out of specification
3
POS.MONITOR
Out of specification
3
Table 42:
CONFIG.MSG; factory setting (Default)
Assign the status signals as follows:
→
/ Select
CONFIG.MSG
.
→
Select
ENTER
. All activated diagnostic functions, which can output a message, are displayed.
→
/ Select required message.
→
Select
ENTER
.
The list of possible status signals is displayed.
→
/ Select required message.
→
Select
SELEC
.
The selected status signal is now marked by a filled circle .
→
Select
EXIT
. Acknowledgment and simultaneous return to the
CONFIG.MSG
menu.
The status signal is now assigned to the diagnostic function.
→
Select
EXIT
. Return to the
DIAGNOSE
main menu.
You have assigned the status signals.
english