Input signals from the control center (e.g. PLC)
Terminal Assignment
On the device side
External circuit / signal level
11 +
Set-point value +
11 +
(0/4...20 mA or 0...5 / 10 V)
fully galvanically isolated
12 -
Set-point value
GND
12 -
GND set-point value
81 +
Binary input +
81 +
+
0...5 V (log. 0)
10...30 V (log. 1)
specific to operating voltage GND (ter-
minal GND)
Table 17:
Terminal assignment; input signals of the control center
12.2.2.2.
Terminal assignment: Output signals to the control center (e.g. PLC)
- (required for analog output and/or digital output option only)
→
Connect terminals according to the variant (options) of the positioner.
Terminal Assignment
On the device side
External circuit / signal level
85 +
Binary output 1
83 +
24 V / 0 V, NC / NO specific to operating
voltage GND (terminal GND)
85 +
Binary output 2
85 +
24 V / 0 V, NC / NO specific to operating
voltage GND (terminal GND)
31 +
Analog fe
31 +
+ (0/4...20 mA or 0...5 / 10 V)
fully galvanically isolated
32 -
Analog feedback GND
32 -
GND analog feedback
Table 18:
Terminal assignment; output signals to the control center
12.2.2.3.
Operating voltage
Terminal Assignment
On the device side
External circuit / signal level
+ 24 V
Operating v
24 V DC ± 10%
max. residual ripple 10%
+ 24 V DC
GND
GND
Operating voltage GND
Table 19:
Terminal assignment; operating voltage