112
Auxiliary functions
Type 8792, 8793 REV.2
→
Select
OK
. Transfer and simultaneous return to the
calibr.POS
menu.
→
/ Select
POS. pMax.
→
Select
INPUT
. The input screen for the upper value (
POS.upper
) is opened.
→
/ Select
OPN
open more
CLS
close more. Approach maximum position of the valve.
→
Select
OK
. Transfer and simultaneous return to the
calibr.POS
menu.
→
Select
EXIT
. Acknowledgment and simultaneous return to the
CAL.USER
menu.
calibr. INP
- Calibration of the set-point position (4...20 mA, 0...20 mA, 0...5 V, 0...10 V):
→
/ Select
calibr.INP
.
→
Select
ENTER
. The menu options for the minimum and maximum value of the input signal are
displayed.
→
/ Select
INP 0 mA (4mA/0V)
. The minimum value for the input signal is displayed.
→
Apply the minimum value to the input.
→
Select
OK
. Transfer and simultaneous return to the
calibr.INP
menu.
→
/ Select
INP 20 mA (5V/10V)
. The maximum value for the input signal is displayed.
→
Apply the maximum value to the input.
→
Select
OK
. Transfer and simultaneous return to the
calibr.INP
menu.
→
Select
EXIT
. Acknowledgment and simultaneous return to the
CAL.USER
menu.
→
Select
EXIT
. Acknowledgment and simultaneous return to the main menu (MAIN).
→
Select
EXIT
. Switching from setting level
process level.
You have calibrated
CAL.USER
.
16.1.17.2. Calibration of the process set-point value and the process actual
value
Calibrate
CAL.USER
as follows:
→
Press
MENU
for 3 s. Switching from process level
setting level.
→
/ Select
CAL.USER
. (To do this, the auxiliary function must be incorporated into the main menu).
→
Select
ENTER
. The submenu options are displayed.
calibr. SP
- Calibration of the process set-point value:
→
/ Select
calibr. SP
.
→
Select
ENTER
. The menu options for the minimum and the maximum process set-point value are
displayed.
→
/ Select
SP 0 mA (4mA/0V)
. The minimum value for the input signal is displayed.
→
Apply the minimum value to the input.
english