123
Auxiliary functions
Type 8792, 8793 REV.2
Simulate the processes and process valve as follows:
→
Press
MENU
for 3 s. Switching from process level
setting level.
→
/ Select
SIMULATION
. (To do this, the auxiliary function must be incorporated into the main menu).
→
Select
ENTER
. The submenu for setting the simulation is displayed.
→
/ Select
CONTROL.sim
.
→
Select
ENTER
.
The submenu for activating and parameterizing the process and process valve simulation is displayed.
→
/ Select required simulation.
Selection
x.SIM
= simulation process.
Selection
p.SIM
= simulation process valve.
→
Select
SELEC
. Activate the selection by checking the box or deactivate it by unchecking the
box .
Setting the parameters for simulation of the process and/or the process valve:
→
/ Select
SIM.Gain
. (Amplification factor).
→
Select
INPUT
. The input screen for specifying the amplification factor is opened.
→
/
+
Increase value
<-
Select decimal place and enter value.
→
Select
OK
. Transfer and simultaneous return to the
CONTROL.sim
menu.
→
/ Select
SIM.Delay
(period duration in seconds).
→
Select
INPUT
. The input screen for specifying the cycle duration is opened.
→
/
+
Increase value
<-
Select decimal place and enter value.
→
Select
OK
. Transfer and simultaneous return to the
CONTROL.sim
menu.
→
Select
EXIT
. Return to the
SIMULATION
menu.
→
Select
EXIT
. Return to the main menu (MAIN).
→
Select
EXIT
. Switching from setting level
process level.
You have simulated the process and process valve.