108
Auxiliary functions
Type 8792, 8793 REV.2
16.1.16.3. Setting of the submenu options of
OUT BIN 1 and OUT BIN 2
Open the submenus as follows:
→
Press
MENU
for 3 s. Switching from process level
setting level.
→
/ Select
OUTPUT
(to do this, the auxiliary function must be incorporated into the main menu).
→
Select
ENTER
. The outputs are displayed.
→
/ Select
OUT BIN1/2
→
Select
ENTER
. Submenu options of
OUT BIN 1/2
are displayed.
You have opened the submenus.
•
POS.Dev
- Alarm output for excessively large control deviation of the position controller
•
POS.Lim-1/2 -
Output of the current position with respect to a specified limit position
Set the suboptions
OUT BIN 1
and
OUT BIN 2
:
POS.Dev
- Alarm output for excessively large control deviation of the position controller:
→
/ Select
POS.Dev
→
Select
SELEC
. The input screen for the limit value
(Deviation:)
is opened.
→
/
+
Increase value
-
Reduce value
Enter limit value for permitted control deviation.
Adjustment range: 1...50% (must not be less than the dead band).
→
Select
OK
. Acknowledgment and simultaneous return to the
OUT BIN 1/2
menu.
Then set the required switching status in the
OUT.type
submenu.
POS.Lim-1/2
- Output of the current position with respect to a specified limit position:
→
/ Select
POS.Lim-1/2
→
Select
SELEC
. The input screen for the limit position
(Limit:)
is opened.
→
/
+
Increase value
-
Reduce value
Enter limit position.
Adjustment range: 0...100%.
→
Select
OK
. Acknowledgment and simultaneous return to the
OUT BIN 1/2
menu.
Then set the required switching status in the
OUT.type
submenu.
You have set the submenus.
english
Summary of Contents for 8792
Page 196: ...www burkert com ...