![Bürkert 8792 Operating Instructions Manual Download Page 67](http://html1.mh-extra.com/html/burkert/8792/8792_operating-instructions-manual_2832027067.webp)
67
Start-up
Type 8792, 8793 REV.2
Automatically determining dead band DBND by running
X.TUNE
:
When
X.TUNE
is running, the dead band can be automatically determined depending on the friction
behavior of the actuating drive.
Before running
X.TUNE
, the
X.CONTROL
auxiliary function must be activated by incorporating it into
the main menu (MAIN).
If
X.CONTROL
is not activated, a fixed dead band of 1% is used.
The changed data is saved in the memory (EEPROM) only when there is a switch to the process
level, by leaving the main menu (MAIN) using the left selection key
EXIT
.
Possible error messages when running
X.TUNE:
Display
Causes of error
Remedy
TUNE
err/break
Manual termination of self-optimi-
zation by pressing the
EXIT
key.
X.TUNE locked
The
X.TUNE
function is blocked.
Enter access code.
X.TUNE
ERROR 1
No compressed air connected.
Connect compressed air.
X.TUNE
ERROR 2
Compressed air failure while
Autotune (
X.TUNE
) is running.
Check compressed air supply.
X.TUNE
ERROR 3
Actuator or control system deaeration
side leaking.
Not possible, device defective.
X.TUNE
ERROR 4
Control system aeration side leaking. Not possible, device defective.
X.TUNE
ERROR 5
The rotation range of the position
sensor has exceeded 180°.
Correct attachment of the position sensor
shaft to the actuator (see
chapter
“12.2” and
“12.3”).
X.TUNE
ERROR 6
The end positions for
POS-MIN
and
POS-MAX
are too close together.
Check compressed air supply.
X.TUNE
ERROR 7
Incorrect assignment
POS-MIN
and
POS-MAX.
To determine
POS-MIN
and
POS-MAX
,
move the actuator in the direction indicated
on the display.
X.TUNE
WARNING 1*
Potentiometer is not coupled opti-
mally to the actuator.
An optimum connection can
provide a more accurate position
measurement.
Set the center position as described in
chapter “12.2.4. Aligning lever mechanism”.
* Warning information gives tips for optimized operation. The device is operational even if this warning information is
not observed. Warning information is automatically hidden after several seconds.
Table 29:
X.TUNE; possible error messages
After making the settings described in chapters “23.1” and “23.2”, the positioner (position controller) is
ready for use.
Activation and configuration of auxiliary functions is described in the following chapter “26. Configuring the
auxiliary functions”.