10.4 - Remote operator station wiring: 200V–240V & 400V–480V Delta E Series VFDs (Powerfoil
®
X Series fans)
WARNING: The fan controllers contain high voltage capacitors that take time to discharge after removal of mains supply.
Before working on the fan controller, ensure isolation of mains supply from line inputs at the fan controller’s disconnect if
installed. Wait three (3) minutes for capacitors to discharge to safe voltage levels. Failure to do so may result in personal
injury or death. Darkened display LEDs are not an indication of safe voltage levels.
10- Fan Remote Operator Station (Optional) (cont.)
10k
Ω
NO
.3
.4
NO
.3
.4
RA RB RC
AVI
NPN
MANUAL
AUTO
OFF
M
I1
M
I5
M
I6
DC
M
AC
M
AV
I
10
V
6 conductors, 20AWG minimum
≤100 ft (30.5 m)
Speed Control
Knob
Mode Selection
Knob
BRN
BRN
BLU
BLU
YEL
GRN
GRN
BLK
BLK
WHT
WHT
RED
RED
MANUAL
AUT
O
Parameter
Change to
02-00: First Master Frequency Command
"1" 0 to +10 V from AVI Terminal
02-01: First Operation Command
"1" External Terminals
04-07: Multifunction Input Terminal 5
"20" Communication Command Enable
The following parameter changes are required for proper operation. To modify these parameters, you will need to reconnect the
BAFCon controller (provided with the fan) and contact Customer Service. Tap the menu icon on the BAFCon Home screen, and
then tap
FAN MANAGEMENT
> Fan Name >
Diagnostics
>
VFD Parameters
. Follow the instructions on the screen for contacting
Customer Service.
Jumper wire installation (yellow)
Big
Ass
Fans recommends making the parameter changes listed above prior to remote wiring or jumper wire installation. A new jumper
should be installed between terminals MI5 and MI6.