1 - Introduction (cont.)
1.2 - Big Ass
Fans devices: Method of configuration
Devices
Type of communication
Type of configuration
SM_VECTOR
RS-485 and Ethernet
Auto-Discover and/or Web Config
DELTA_VFD_E
RS-485 and Ethernet
Auto-Discover and/or Web Config
DELTA_VFD_M
RS-485 and Ethernet
Auto-Discover and/or Web Config
AB_PF4_40
Ethernet
Web Config Only
AB_PF4M
Ethernet
Web Config Only
Figure 1: Method of configuration for the devices
1.3 - Big Ass Fans devices and point count available
When installing the ProtoNode, be aware of the total combined points of the devices being connected to the ProtoNode.
The total
number of devices attached to ProtoNode RER (FPC-N34) cannot exceed 1200 Modbus registers for BACnet MS/TP, BACnet/
IP, Modbus/TCP or Metasys N2.
Devices
Point count
SM_VECTOR
19
DELTA_VFD_E
12
DELTA_VFD_M
12
AB_PF4_40
13
AB_PF4M
13
Figure 2: Modbus registers
1.4 - BTL Mark: BACnet Testing Laboratory
The BTL Mark on ProtoNode RER is a symbol that indicates that a product has passed a series of rigorous
tests conducted by an independent laboratory which verifies that the product correctly implements the
BACnet features claimed in the listing. The mark is a symbol of a high-quality BACnet product. Go to
http://www.bacnetinternational.net/btl/ for more information about the BACnet Testing Laboratory.