2 - BACnet Setup (cont.)
2.5 Set baud rate
Set the baud rate for BACnet MS/TP on ProtoNode RER (FPC-N34 BACnet).
2.5.1 - Setting the serial baud rate
Set the serial baud rate (DIP switch B0–B3) for BACnet MS/TP.
•
DIP switches B0–B3 can be used to set the serial baud rate to match the baud rate provided by the Building Management System
for BACnet MS/TP.
•
The baud rate on the ProtoNode for Metasys N2 is set for 9600. DIP switches B0–B3 are disabled for Metasys N2 on ProtoNode
RER (FPC-N34).
B0 B1 B2 B3
Figure 8: Baud rate DIP switches
2.5.1.1 - Baud rate DIP switch selection
Baud
B0
B1
B2
B3
9600
On
On
On
Off
19200
Off
Off
Off
On
38400
On
On
Off
On
57600
Off
Off
On
On
76800
On
Off
On
On
Figure 9: Baud rate