35
WWW.BIGASSFANS.COM ©2013 DELTA T LLC ALL RIGHTS RESERVED
10 - Fan Remote Operator Station (Optional) (cont.)
10-100k
Ω
(0-5VDC)
10-100k
Ω
(0-5VDC)
M
AN
UA
L
AU
TO
NO
.3
.4
NO
.3
.4
NO
.3
.4
NO
.3
.4
U
/
T1
V
/
T2
W
/
T3
PE
L1
L2
N
2 TXA TXB 11
12V 1 13A 13B 13C 16 17
AI
2
30
MANUAL
AUTO
OFF
MANUAL
AUTO
OFF
10.6 - Remote operator station wiring: Lenze SMVector VFDs (Powerfoil
®
8 & Basic 6
®
fans)
WARNING: The fan controllers contain high voltage capacitors that take time to discharge after removal of mains supply.
Before working on the fan controller, ensure isolation of mains supply from line inputs at the fan controller’s disconnect
if installed. Wait three (3) minutes for capacitors to discharge to safe voltage levels. Darkened display LEDs are not an
indication of safe voltage levels.
The following parameter changes are required for proper operation:
Parameter
Default setting
Change to
P100: Start Stop Control
3
1
P116: Remote Speed Reference
6
1
P123: TB13C Function
0
7
P140: Relay Function
3
16
P156: Analog In Config
0
1
Jumper wire installation (yellow)
Big
Ass
Fans recommends making the parameter changes listed above prior to remote wiring or jumper wire installation. Jumpers
should be installed between terminals 1 and 17, terminals 13B and 13C, and terminals 12V and 16. If an ESFR pilot relay is already
installed on terminals 12V and 13A, remove the N.O. relay common lead from terminal 12V and relocate to terminal 16. This will
prevent three wires from being landed under a single terminal. In this control arrangement, terminals 12V and 16 are both +12 VDC for
digital supply.
Both jumpers (1 to 12V, 1 to 13B) must be removed if present!
6 conductors, 20 AWG minimum
BLU
GRN
BLK
RED
WHT
BRN
YEL
BRN
BLU
GRN
BLK
WHT
RED
≤100 ft (30.5 m)
Speed Control
Knob
Mode Selection
Knob