Appendix D.1 - Specifications
Electrical
connections
One 6-pin Phoenix connector, one RS-485 +/- ground port, power +/- frame ground port
One 3-pin RS-485 Phoenix connector, one RS-485 +/- ground port
One Ethernet-10/100 Ethernet port
Approvals
Pending CE (EN55022; EN55024; EN60950), UL916, Pending FCC Class A Part 15, DNP3 Conformance
Tested, OPC Self-tested for Compliance, RoHS Compliant, CSA 205 Approved
BTL Marked
Power
requirements
Multi-mode power adapter: 9–30VDC or 12–24VAC
Physical
dimensions
11.5 cm L x 8.3 cm W x 4.1 cm H (4.5" x 3.2" x 1.6")
Weight
0.2 kg (0.4 lbs)
Operating
temperature
-40°C to 75°C (-40°F to 167°F)
Surge
suppression
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Humidity
5–90% RH (non-condensing)
Specifications subject to change without notice.
Appendix D.2 - Compliance with UL regulations
For UL compliance, the following requirements must be met when operating the ProtoNode:
•
The unit shall be powered by a listed LPS or Class 2 power supply suited to the expected operating temperature range.
•
The interconnecting power connector and power cable shall:
•
Comply with local electrical code.
•
Be suited to the expected operating temperature range.
•
Meet the current and voltage rating for ProtoNode/Net.
•
The interconnecting power cable shall:
•
Be of length not exceeding 3.05 m (118.3”)
•
Be constructed of materials rated VW-1 or FT-1 or better
•
If the unit is to be installed in an operating environment with a temperature above 65°C (149°F), it should be installed in a Restricted
Access Area requiring a key or a special tool to gain access.
•
The device must not be connected to a LAN segment with outdoor wiring.
Figure 33: Specifications