WWW.BIGASSFANS.COM ©2013 DELTA T LLC ALL RIGHTS RESERVED
34
10.5 - Remote operator station wiring: 575V–600V Delta M Series VFDs (Powerfoil
®
X Series fans)
WARNING: The fan controllers contain high voltage capacitors that take time to discharge after removal of mains supply.
Before working on the fan controller, ensure isolation of mains supply from line inputs at the fan controller’s disconnect if
installed. Wait three (3) minutes for capacitors to discharge to safe voltage levels. Failure to do so may result in personal
injury or death. Darkened display LEDs are not an indication of safe voltage levels.
The following additional parameter changes are required for proper operation:
Jumper wire installation (shown above in yellow)
Big
Ass
Fans recommends making the parameter changes listed above prior to remote wiring or jumper wire installation. A new jumper
should be installed between terminals M4 and M5.
10k
Ω
NO
.3
.4
NO
.3
.4
U
T1
V
T2
W
T3
Brake
B1
B2
U
T1
V
T2
W
T3
Brake
B1
B2
MANUAL
AUTO
OFF
ENTER
STOP
RESET
1.5KW
VFD-M
M
0
M
4
M
5
GN
D
10
V
AV
I
GN
D
6 conductors, 20AWG minimum
≤100 ft (30.5 m)
Parameter
Change to
Pr.00: First Start/Stop Reference
"1" Master Freq. from 0 to +10V
Pr.01: First Speed Reference
"1" Master Start/Stop from Ext. Terminals
Pr.41: Multifunction Input Terminal 4
"24" Control Source = Communication
Pr.42: Multifunction Input Terminal 5
"28" 2nd Source for Frequency Command
Speed Control
Knob
Mode Selection
Knob
10 - Fan Remote Operator Station (Optional) (cont.)
BRN
BRN
BLU
BLU
YEL
GRN
GRN
BLK
BLK
WHT
WHT
RED
RED