19
WWW.BIGASSFANS.COM ©2013 DELTA T LLC ALL RIGHTS RESERVED
WARNING: To reduce the risk of electric shock, wiring should be performed by a qualified electrician! Incorrect assembly can
cause electric shock or damage the motor and the controller! Hazard of electrical shock!
WARNING: Installation must be in accordance with the requirements specified in this installation manual and with any
additional requirements set forth by the National Electric Code (NEC), ANSI/NFPA 70-2011, and all local codes. Code
compliance is ultimately YOUR responsibility! Failure to comply with these codes could result in personal injury or property
damage.
WARNING: The fan controllers contain high voltage capacitors that take time to discharge after removal of mains supply.
Before working on the fan controller, ensure isolation of mains supply from line inputs at the fan controller’s disconnect if
installed. Wait three (3) minutes for capacitors to discharge to safe voltage levels. Failure to do so may result in personal
injury or death. Darkened display LEDs are not an indication of safe voltage levels.
CAUTION: The Big Ass Fans product warranty will not cover equipment damage or failure that is caused by improper
installation.
Powerfoil X Series
Serial Address #1
Powerfoil X Series
Serial Address #2
Basic 6 or Powerfoil8
Serial Address #3
Powerfoil X Series
Max Serial Address #32
Gateway
Location
Wall-Mounted
Fan Controller
EOL Resistor
Required
Powerfoil X Series
Serial Address #1
Powerfoil X Series
Serial Address #2
Powerfoil X Series
Serial Address #3
Basic 6 or Powerfoil8
Serial Address #4
Basic 6 or Powerfoil8
Max Serial Address #32
Wall-Mounted
Fan Controller
EOL Resistor
Required
EOL Resistor
Required
Modbus cable
Modbus cable
Modbus cable
Modbus cable
Modbus cable
Modbus cable
Gateway
Location
9.1 - Modbus wiring overview
The Modbus RTU protocol is used for communication with fans over a two-wire RS-485 network. Each fan or device requires a unique
serial address. The following pages detail the setup and connections unique to each supported type of fan. Two basic wiring layouts are
shown below. The first illustrates multiple daisy chained drops with the gateway located on one end of the Modbus loop. The second
illustrates the same fan drop arrangement with the gateway in a central location. Either scenario will handle up to 32 unique serial
addresses.
9 - Big Ass Fans Electrical Installation
Do not assign the same address to two (2) fans.