Plexus 9000 Planning and Engineering Guide
Interconnect Drawings
Section 130-250-000
Issue 3, January 24, 2003
Telica, Inc.
7-19
The DS-1, J1 or E1 cables typically terminate at a cross-connect, via either
wire-wrap,
. Refer to
for the channel designation pinout and wire color-coding.
The cable distance to the cross-connect panel cannot be greater than 655
feet when using 22-gauge T1 cable and no greater than 400 feet when
using 24-guage T1 cable. DS1/J1/E1 cabling in a rack is shown in
The DS-1, J1 or E1 can be Inter-Machine Trunks (IMTs), ISDN Primary
Rate Interfaces (PRIs) or SS7 Signaling Links. To provide redundancy for
the SS7 links, two IOMs modules are typically used.
P237-AA
07-19-00
MALE
1
33
32
64
Figure 7-17. 64-pin AMP-style Cable – Connector to Wire-wrap
P238-AA
07-19-00
MALE
1
33
32
64
1
33
32
64
MALE
Figure 7-18. 64-pin AMP-style Cable – Connector to Connector