Packet Network Access Module
Plexus 9000 Installation and Operations Manual
Issue 1, May 28, 2004
Section 130-120-760
5-192
Telica,
Inc.
5.17.4 Specifications
Table 5.17-B. Environmental Specifications
Environmental
Conditions
Temp. (°F)
Min/Max
Temp. (°C)
Min/Max
Relative
Humidity
Standard temperature
operation
+41 to +104
+5 to +40
Up to 85%
non-condensing
Standard temperature
short term operation
+23 to +122
-5 to +50
Up to 95%
non-condensing
Standard temperature
storage
-40 to +158
-40 to +70 Up to 95%
non-condensing
Operational altitude
From 200 feet below sea level to 13,000 above
sea level.
Notes
:
1. Temperature ranges refer to the conditions 5 feet above the
bottom of the equipment rack in which the unit is mounted, and
15 inches in front of the unit.
2. Short-term operation refers to a period of not more than 96
consecutive hours, with a total of not more than 15 days per year.
1