www.baldormotion.com
3-22 Basic Installation
MN1942
3.5.6 Motor brake connection
You might wish to wire a motor’s brake, via relays, to digital outputs on connector X3 (see section
3.3.1). This provides a way for the MicroFlex
e
100 to control the motor’s brake. A typical circuit
is shown in Figure 10.
C
D
from motor brake
connections
Separate
customer
supplied
24 VDC supply
Relay 2
Relay 1
+24 V
0 V
The inner shield
surrounding the
brake wires should
be earthed/grounded
at one point only.
The relays have normally open
contacts and are shown deactivated
(contacts open, brake engaged).
DOUT0+
DOUT0-
11
1
DOUT1+
DOUT1-
13
3
User supply V+
User supply GND
‘X3’
Figure 10 - Motor brake control circuit
This circuit uses the drive enable signal (configured using
DRIVEENABLEOUTPUT
to appear on
DOUT0) in conjunction with DOUT1 (configured as the
MOTORBRAKEOUTPUT
). See the Mint help
file for details. With this configuration, the following sequences can be used to control the brake.
To engage the brake:
H
The motor is brought to rest under normal control;
H
Relay 2 is deactivated, causing the brake to engage;
H
The drive is disabled. This removes power from the motor and causes Relay 1 to be
deactivated.
To disengage the brake:
H
The drive is enabled, activating Relay 1;
H
Power is applied to the motor to hold position under normal control;
H
Relay 2 is activated, causing the brake to be disengaged.
It may be necessary to include a small delay, after Relay 2 has been activated, before starting
motion. This delay will allow time for the relay contacts to engage and the brake to release.
The 24 VDC power supply used to power the brake must be a separate supply as
shown in Figure 10. Do not use the supply that is powering the MicroFlex
e
100
digital outputs. The brake wires often carry noise that could cause erratic drive
operation or damage. The brake contacts must never be wired directly to the
digital outputs. The relay(s) should be fitted with a protective flyback diode, as
shown. The separate 24 VDC supply used for the motor brake may also be used
to power the relay in the thermal switch circuit (section 3.5.5).
CAUTION
Summary of Contents for MicroFlex e100
Page 1: ......
Page 2: ......
Page 14: ...www baldormotion com 2 4 Introduction MN1942...
Page 80: ...www baldormotion com 5 26 Input Output MN1942...
Page 108: ...www baldormotion com 6 28 Configuration MN1942...
Page 116: ...www baldormotion com 7 8 Troubleshooting MN1942...
Page 124: ...www baldormotion com 8 8 Specifications MN1942...
Page 142: ...www baldormotion com B 6 Control System MN1942...
Page 170: ...Comments MN1942 Thank you for taking the time to help us...
Page 171: ......
Page 172: ......