3.4.5 Recommended fuses, circuit breakers and wire sizes
Table 3 describes the recommended fuses, circuit breakers and suitable wires sizes to be used
for power connections.
Catalog
Cont.
AC
Input Fuse
Circuit
Minimum
Catalog
Number
Cont.
Output
A
AC
Supply
T
Input Fuse
Circuit
breaker
(C t
)
Minimum
Wire Gauge
p
Amps
(RMS)
pp y
Type
(C-type)
AWG
mm
2
1
Φ
Ferraz Shawmut:
6x32 FA series, 10 A (W084314P)
10 A
14
2 0
MFE A003
3 A
1
Φ
6x32 FA series, 10 A (W084314P)
or
BS88 2.5 URGS 10 A (N076648)
10 A
14
2.0
MFE..A003
3 A
3
Φ
Ferraz Shawmut:
6x32 FA series, 8 A (V084313P)
8 A
14
2 0
3
Φ
6x32 FA series, 8 A (V084313P)
or
BS88 2.5 URGS, 7 A (M076647)
8 A
14
2.0
1
Φ
Ferraz Shawmut:
6x32 FA series, 20 A (A084318P)
20 A
14
2 0
1
Φ
6x32 FA series, 20 A (A084318P)
or
BS88 2.5 URGS, 20 A (L097507)
20 A
14
2.0
MFE..A006
6 A
3
Φ
Ferraz Shawmut:
6x32 FA series, 12.5 A
(X084315P)
12 5 A
14
2 0
3
Φ
(X084315P)
or
BS88 2.5 URGS, 12 A (P076649)
12.5 A
14
2.0
1
Φ
Ferraz Shawmut:
25 A
14
2 5
1
Φ
Ferraz Shawmut:
BS88 2.5 URGS, 25 A (R076651)
25 A
14
2.5
MFE..A009
9 A
3
Φ
Ferraz Shawmut:
6x32 FA series, 20 A (A084318P)
20 A
14
2 0
3
Φ
6x32 FA series, 20 A (A084318P)
or
BS88 2.5 URGS, 20 A (L097507)
20 A
14
2.0
Table 3 - Protection device and wire ratings
Note:
All wire sizes are based on 75 °C (167 °F) copper wire. Higher temperature smaller
gauge wire may be used per National Electric Code (NEC) and local codes.
Recommended fuses are based on 25 °C (77 °F) ambient, maximum continuous
control output current and no harmonic current. Earth/ground wires must be the
same gauge, or larger, than the Line wires.
3.4.6 Drive overload protection
The MicroFlex
e
100 will immediately trip and disable if there is an overload condition. The
parameters for managing drive overloads are configured automatically by the Commissioning
Wizard (see section 6.4.3). If they need to be changed, use the Parameters tool in Mint
WorkBench (see section 6.5.2).
Summary of Contents for MicroFlex e100
Page 1: ......
Page 2: ......
Page 14: ...www baldormotion com 2 4 Introduction MN1942...
Page 80: ...www baldormotion com 5 26 Input Output MN1942...
Page 108: ...www baldormotion com 6 28 Configuration MN1942...
Page 116: ...www baldormotion com 7 8 Troubleshooting MN1942...
Page 124: ...www baldormotion com 8 8 Specifications MN1942...
Page 142: ...www baldormotion com B 6 Control System MN1942...
Page 170: ...Comments MN1942 Thank you for taking the time to help us...
Page 171: ......
Page 172: ......