www.baldormotion.com
Basic Installation 3-21
MN1942
3.5.5 Thermal switch connection
You might wish to wire the motor’s thermal switch contacts (normally closed), using a relay, to a
digital input on connector X3 (see section 3.3.1). Using the Mint WorkBench Digital I/O tool, the
input can be configured to be the motor trip input. This allows the MicroFlex
e
100 to respond to
motor over-temperature conditions. The Mint keyword
MOTORTEMPERATUREINPUT
can also be
used to configure a digital input for this purpose. A typical circuit, using DIN1 as the input, is shown
in Figure 9.
A
B
motor
thermal
switch
Relay
Customer
supplied
24 VDC
supply
+24 V
0 V
Separate
customer
supplied
24 VDC supply
+24 V
0 V
DIN1+
DIN1-
16
6
‘X3’
The relay has normally open
contacts and is shown deactivated
(contacts open, motor overheated).
Figure 9 - Motor thermal switch circuit
The 24 VDC power supply connected to the thermal switch must be a separate
supply as shown in Figure 9. Do not use the 24 VDC supply used for the drive
enable signal, or the internally generated supply (if present). The thermal switch
wires often carry noise that could cause erratic drive operation or damage. The
thermal switch contacts must never be wired directly to a digital input or any part
of the logic supply for other components in the system.
The separate 24 VDC supply used for the thermal switch may also be used for the
motor brake circuit (section 3.5.6).
CAUTION
Summary of Contents for MicroFlex e100
Page 1: ......
Page 2: ......
Page 14: ...www baldormotion com 2 4 Introduction MN1942...
Page 80: ...www baldormotion com 5 26 Input Output MN1942...
Page 108: ...www baldormotion com 6 28 Configuration MN1942...
Page 116: ...www baldormotion com 7 8 Troubleshooting MN1942...
Page 124: ...www baldormotion com 8 8 Specifications MN1942...
Page 142: ...www baldormotion com B 6 Control System MN1942...
Page 170: ...Comments MN1942 Thank you for taking the time to help us...
Page 171: ......
Page 172: ......