Troubleshooting 7-3
MN1942
7.2.2 CAN LEDs
The CAN LEDs display the overall condition of the CANopen interface,
once the startup sequence has completed. The LED codes conform to
the CAN in Automation (CiA) DR303_3 indicator standard. The green
LED indicates the state of the node’s internal CANopen ‘state machine’.
The red LED indicates the state of the physical CANopen bus.
Green (run)
X
Off: Node initializing or not powered.
1 flash: Node in STOPPED state.
3 flashes: Software is being downloaded to the node.
Continuous flashing: Node in PRE-OPERATIONAL state.
Flickering (very fast flashing): Auto-baudrate detection or LSS services in
progress; flickers alternately with red LED.
Continuously illuminated, not flashing: Node in OPERATIONAL state.
Red (error)
X
Off: No errors or not powered.
1 flash: Warning - too many error frames.
2 flashes: Guard event or heartbeat event has occurred.
3 flashes: The SYNC message has not been received within the timeout period.
Flickering (very fast flashing): Auto-baudrate detection or LSS services in
progress; flickers alternately with green LED.
Continuously illuminated, not flashing: The node’s CAN controller is in the BUS
OFF state, preventing it from taking part in any CANopen communication.
Summary of Contents for MicroFlex e100
Page 1: ......
Page 2: ......
Page 14: ...www baldormotion com 2 4 Introduction MN1942...
Page 80: ...www baldormotion com 5 26 Input Output MN1942...
Page 108: ...www baldormotion com 6 28 Configuration MN1942...
Page 116: ...www baldormotion com 7 8 Troubleshooting MN1942...
Page 124: ...www baldormotion com 8 8 Specifications MN1942...
Page 142: ...www baldormotion com B 6 Control System MN1942...
Page 170: ...Comments MN1942 Thank you for taking the time to help us...
Page 171: ......
Page 172: ......