126
14.6.41
Example 2 - Control TA / TP
Let's see how to set a filter on the data received in order to check the status of bits TA and TP.
For example if we want an alarm to the radio (which supports the service TA) has the TA = On for a period longer than
10 minutes.
We set the filter:
ChanRef = 4
Block1Ref = xxxxxxxxxxxxxxxx (we do not care this time of the IP)
Block2Ref = 000001XXXXX0XXXX (group 0A - TP = 1 - TA = 0)
Block3Ref = xxxxxxxxxxxxxxxx (we do not treat)
Block4Ref = xxxxxxxxxxxxxxxx (we do not treat)
Timeout = 1200s
Validation
=10s
Hold
=10s
Mask
=Unmasked
Trap
=Enabled
An alarm is generated if TA remains unchanged equal to 0 for 20 min
Starting from TP=1 and TA=0
When TA = 1, after the set time, the filter goes into alarm: