AUX-Light CAC 50Hz R410A
Trouble shooting
86
Model
AL-H36/4R1(U)
AL-H36/5R1D(U)
Factory Model
AL-H36A4/R1(T)
AL-H36A5/R1(T)-B7
Code
16107022000001
16107022000020
Power Supply
V~,Hz
,Ph
380~415,50,3
380~415,50,3
Max. Input Consumption
W
5200
5100
Max. Current
A
17.8
9.50
Capacity
Cooling
Btu/h
36000
36000
kW
10.6
10.55
Heating
Btu/h
37500
40000
kW
10.9
11.70
Compressor
Model
ATE498SC3Q9RK1
ATH420UC-C9EU
Type
Twin Rotary
Twin Rotary
Brand
HIGHLY
HIGHLY
Capacity
W
12650
10150
Input
W
4130
3350
Rated Current(RLA)
A
7.2
6.9
Locked Rotor Amp(LRA)
A
69
66
Thermal Protection temp.
160
180
Capacitor
uF
/
/
Refrigerant Oil
ml
1600
840
Outdoor Fan
Motor
Model
YDK150-6C
YDK150-6C-420
code
/
/
Brand
HUATE
Weiling
Output Power x Fan Quantity
W
150×1
150×1
Capacitor
uF
6
6
Speed
r/min
820
820
Coil
Number Of Rows
2
2
Tube Pitch(a)x Row Pitch(b)
mm
22×19.05
22×19.05
Fin Pitch
mm
1.4
1.4
Fin Material
Hydrophilic aluminum fin
Hydrophilic aluminum fin
Tube Outside Dia.and Type
mm
φ7.94
,
Inner grooved
φ7
,
Inner grooved
Coil Length x Height x Width
mm
878×814×38.1
894×814×38.1
Heat Exchanging Area
m2
30.3
35.30
Air Flow Volume
CFM
1876
1876
m
3
/h
3190
3190
Noise Level
dB(A)
60
62
Dimension
(W×D×H)
Net
mm
903×354×857
903×354×857
Packing
mm
1030×410×980
1030×410×980
Weight
Net
kg
72
71
Gross
kg
83
81
Refrigerant
Type/Quantity
Type
R410A
R410A
Charged Volume
g
2300
2150
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...