AUX-Light CAC 50Hz R410A
Trouble shooting
109
Additional refrigerant charge
When pipe length exceeds 5m, please add refrigerant according to the table below:
Connection
piping
Piping size)
Additional refrigerant
charge amount (kg/m)
Gas pipe
Liquid pipe
Piping
between
indoor and
outdoor unit
φ9.52×0.75mm
φ6.35×0.75mm
0.02
φ12.7×1mm
φ6.35×0.75mm
0.03
φ15.88×1mm
φ9.52×0.75mm
0.05
φ19.05×1mm
φ9.52×0.75mm
0.07
φ19.05×1mm
φ12.7×1mm
0.09
Others
Users to install the air conditioner at site shall ensure that the oil can return to the unit smoothly.
◇
Horizontal pipes should incline toward the outdoor unit using a 20:1 slop.e
◇
If there is a height difference between the indoor and outdoor unit, oil loops should be installed in the inter
connecting gas (large) pipe;
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...