AUX-Light CAC 50Hz R410A
Trouble shooting
125
6.Failure code display
When air condition has failure, the timing lamp on light board of controller will display different code
according to different failure case.
6.1 Unit failure code for unit power supply is 220-240V
Failure causing
Display mode 1
(indication lamp on display
lamp board)
Display mode 2
(wired controller)
Display
priority
Phenomenon
Communication failure
none
E5
1
shutdown
Drainage system failure
Timing lamp flash 4
times/8s
E4
2
shutdown
Phase failure, phase-loss or low
voltage failure
Timing lamp lash 6
times/8s
E6
3
shutdown
Indoor temperature sensor
abnormal (TA)
Timing lamp flash 1
times/8s
E1
4
shutdown
Indoor coil sensor abnormal(TE)
Timing lamp flash 2
times/8s
E3
5
shutdown
Outdoor coil sensor
abnormal(TW)
Timing lamp flash 2
times/1s
E2
6
non-stop
Indoor heating over-load
protection
None
7
shutdown
Defrosting(not failure)
Operation lamp flash
None
8
non-stop
6.2 Unit failure code for unit power supply is 380-415V
Failure causing
Display mode1
(indication lamp on
display lamp board)
Display mode1
(failure lamp on
control board)
Display
mode3
(wired
controller)
Display
priority
Phenomenon
Communication failure
Flash 5 times and go out
2S
Flash 2 times
and go out 2S
F1
1
shutdown
Wired controller
communication failure
-
-
E5
1
shutdown
Drainage system failure
Flash 4 times and go out
2S
-
E4
3
shutdown
Outdoor protection( Phase
failure )
Flash6 times and go out
2S
-
E6
2
shutdown
Outdoor protection
(discharging
over-temperature )
Flash 10 times and go
out 2S
Flash 10 times
and go out 2S
EA
7
shutdown
High pressure protection
Flash 9 times and go out
2S
Flash 1 times
and go out 2S
E9
6
shutdown
Low pressure protection
Flash 9 times and go out
2S
Flash 3 times
and go out 2S
E9
6
shutdown
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...