AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
28
This is as shown in the drawing as follows:
◇
Adjust the relative position of the suspension hook on the suspension bolt so that the unit can be in
level position in all directions. Check with a level gauge after installation to ensure that the indoor unit
is horizontal, otherwise it will cause water leakage, air leakage etc.
◇
Tighten the bolt and ensure that four hooks are in close contact with the nuts and washers, to fix the
indoor unit under the ceiling.
◇
After the unit is installed ensure it is secure and does not shake or sway.
◇
Ensure that the centre of the indoor unit is in alignment with the centre of the opening in the ceiling.
6.6 Drainage pipe installation
◇
The drainage pipe should be properly insulated to prevent the generation of condensation. Heat
insulation material: the thickness of rubber insulation pipe should be more than 8mm
◇
Drainage pipe must have a downward gradient (1 / 50 1 / 100) to avoid water backflow or leakage etc.
◇
The unit has a drain pump which will lift up to 1200mm. However after the pump stops the water left in
the pipe will drain back and may overflow the drain tray causing water leakage. For this reason please
install the drain pipe as shown.
More than 1:100
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...