AUX-Light CAC 50Hz R410A
Universal outdoor unit
67
3.Capacity amendment
3.1 Amendment coefficient of cooling capacity under different indoor/outdoor DB and WB
Indoor temperature°C
Outdoor air inlet DB°C
DB
WB
25
30
35
40
43
45
47
49
23
16
0.98
0.94
0.89
0.85
0.82
0.79
0.74
0.71
25
18
1.05
1
0.95
0.90
0.87
0.82
0.77
0.72
27
19
1.1
1.05
1
0.95
0.91
0.87
0.84
0.79
28
20
1.12
1.07
1.02
0.96
0.93
0.90
0.86
0.81
30
22
1.19
1.13
1.08
1.02
0.99
0.96
0.91
0.88
32
24
1.26
1.20
1.15
1.08
1.05
1.02
0.97
0.92
Actual cooling capacity calculation:
Actual cooling capacity=amendment coefficient of cooling capacity × nominal cooling capacity
——nominal cooling capacity could be found from the performance parameters list
——amendment coefficient of cooling capacity could be found from table above.
3.2 Amendment coefficient of heating capacity under different indoor/outdoor DB and WB
Actual heating capacity calculation:
Actual heating capacity=amendment coefficient of heating capacity × nominal heating capacity
——nominal heating capacity could be found from the performance parameters list
——amendment coefficient of heating capacity could be found from table above.
Indoor DB°C
Outdoor air inlet WB°C
-15
-10
-5
0
6
10
15
16
0.45
0.53
0.65
0.80
1.02
1.13
-
18
0.47
0.55
0.61
0.76
1.02
1.12
-
20
0.46
0.54
0.6
0.75
1
1.11
1.25
21
0.42
0.49
0.59
0.72
0.99
1.1
1.24
22
0.41
0.49
0.58
0.71
0.97
1.09
1.23
24
0.39
0.45
0.56
0.7
0.96
1.08
1.22
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...