AUX-Light CAC 50Hz R410A
Universal outdoor unit
63
2.Specfication
Model
Indoor Unit
ALMD-H18/4R1D
ALMD-H24/4R1D
ALMD-H36/4R1
Outdoor Unit
AL-H18/4R1D(U)
AL-H24/4R1D(U)
AL-H36/4R1(U)
Factory Model
Indoor Unit
ALHi-H18A4/R1S
3-B7
ALHi-H24B4/R1S3-
B7
ALHi-H36A4/R1-S
3
Outdoor Unit
AL-H18A4/R1(T)-
B7
AL-H24A4/R1(T)-B7
AL-H36A4/R1(T)
Code
Indoor Unit
16113022000047
16113022000043
16113022000025
Outdoor Unit
16107022000019
16107022000018
16107022000001
Power Supply
V~,Hz,
Ph
220~240,50,1
220~240,50,1
220~240,50,1
Capacity
Cooling
Btu/h
18000
24000
36000
kW
5.3
7.2
10.6
Heating
Btu/h
20000
27500
37500
kW
5.8
8.1
10.9
Electric Data
Rated Cooling Power Input
kW
1.73
2.39
3.62
Rated Heating Power Input
kW
1.79
2.35
3.59
Rated Cooling Current
A
7.95
10.37
6.80
Rated Heating Current
A
8.22
10.89
6.50
Performance
EER
W/W
3.06
3.01
2.81
COP
W/W
3.24
3.44
3.34
Indoor Fan
Fotor
Model
YSK100-4
YSK160-4
YSK180
-4
Brand
Weiling
Sanxiang/Kangbao
Kangbao
Output Power x Fan
Quantity
W
100
160
180
Capacitor
uF
4
2.5
6
Speed (Hi/Mi/Lo)
r/min
960/860/840
1050/1000/910
1200/1120/1060
Indoor Coil
Number Of Rows
2
3
3
Tube Pitch(a)x Row
Pitch(b)
mm
20.5×12.7
20.5×12.7
20.5×12.7
Fin Spacing
mm
1.5
1.6
1.6
Fin Material
Hydrophilic aluminum fin
Tube Outside Dia.and Type mm
φ7
,
Inner
grooved
φ7
,
Inner grooved
φ7
,
Inner grooved
Coil Length x Height x
Width
mm
625×369×25.4
625×369×38.1
625×369×38.1
Heat Exchanging Area
m
2
6.98
9.87
9.87
Indoor Unit
Indoor Air Flow (Hi/Mi/Lo)
m
3
/h
1000/800/700
1400/1120/980
2000/1600/1400
Noise Level(Hi/Mi/Lo)
dB(A)
44/41/35
47/44/38
50/47/41
External Static Pressure
Pa
50/80
50/80
50/80
Net Dimension (W*H*D)
mm
890×785×290
890×785×290
890×785×290
Packing
Dimension(W*H*D)
mm
1100×870×360
1100×870×360
1100×870×360
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...