AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
29
◇
When draining multiple units into a common drain line, this common drain should be installed about
100mm below each units drain outlet, as shown in the drawing.
◇
When finish installation please carry out the drainage test to ensure that the water flow through the
pipeline fluently, and carefully observe the junction to ensure that there is no water leakage. If the unit
is installed in the newly built house, strongly recommend that this test taken before the ceiling
installation. Even it is the heating only unit, this test is unavoidable.
6.7 Panel installation
◇
As to the MB12 panel please refer to the following picture, the panel has four hooks which attach to
corresponding hangers on the unit and the panel should be positioned using these first. The panel is
then fixed into position by four bolts which are accessed through the four corner panels on the grille.
6.8 Connect duct, fresh air ventilation
In order to meet different customers’ requirements and their different usage environment, indoor unit
reserves one fresh air ventilation hole and four duct connection holes. The fresh air can be introduced
from outside or through duct.
Less than 300mm
Less than 600mm
(Unit: mm)
L
e
s
s
t
h
a
n
8
0
0
m
m
M
o
re
th
a
n
1
00
mm
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...