AUX Light Commercial Air Conditioners T1,50Hz, R410a,ON/OFF
41
Model
Indoor Unit
ALCF-H48/5R1C
ALCF-H60/5R1C
Outdoor Unit
AL-H48/5R1D(U)
AL-H60/5R1D(U)
Factory Model
Indoor Unit
ALCe-H48A5/R1C5-B7
ALCe-H60A5/R1C5-B7
Outdoor Unit
AL-H48A5/R1(T)-B7
AL-H60A5/R1(T)-B7
Factory Model
Indoor Unit
16109022000009
16109022000010
Outdoor Unit
16107022000022
16107022000023
Power Supply
V~,Hz,Ph
380~415,50,3
380~415,50,3
Capacity
Cooling
Btu/h
48000
60000
kW
14.0
17.6
Heating
Btu/h
53000
63500
kW
15.5
18.5
Electric Data
Rated Cooling Power
Input
kW
4.87
5.71
Rated Heating Power
Input
kW
5.13
5.97
Rated Cooling Current
A
8.88
10.42
Rated Heating Current
A
9.33
10.83
Performance
EER
W/W
2.87
3.08
COP
W/W
3.02
3.10
Indoor Fan Fotor
Model
YSK-105W-4
YSK-105W-4
Brand
Weiling
Weiling
Output Power x Fan
Quantity
W
105
105
Capacitor
uF
5
4
Speed (Hi/Mi/Lo)
r/min
1387/1108/970
1387/1108/970
Indoor Coil
Number Of Rows
3
3
Tube Pitch(a)x Row
Pitch(b)
mm
20.5×12.7
22×19.05
Fin Spacing
mm
1.6
1.6
Fin Material
Hydrophilic
aluminum fin
Hydrophilic aluminum fin
Tube Outside Dia.and
Type
mm
φ7,Inner grooved
φ7.94,Inner grooved
Coil Length x Height x
Width
mm
1300×246×38.1
1300×242×57.15
Heat Exchanging Area
m
2
13.69
20.55
Indoor Unit
Indoor Air Flow
(Hi/Mi/Lo)
m
3
/h
1800/1440/1260
1800/1440/1260
Noise Level(Hi/Mi/Lo)
dB(A)
51/48/42
51/48/42
Net Dimension
(W*H*D)
mm
1631×660×205
1631×660×205
Packing Dimension
mm
1710×720×290
1710×720×290
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...