AUX-Light CAC 50Hz R410A
Trouble shooting
88
Motor
code
/
/
Brand
Sinjun/Welling
Sinjun/Welling
Output Power x Fan Quantity
W
60×2
60×2
Capacitor
uF
3.5×2
3.5×2
Speed
r/min
750
750
Coil
Number Of Rows
1.5
1.5
Tube Pitch(a)x Row Pitch(b)
mm
22×19.05
22×19.05
Fin Pitch
mm
1.4
1.4
Fin Material
Hydrophilic aluminum fin
Hydrophilic aluminum fin
Tube Outside Dia.and Type
mm
φ7
,
Inner grooved
φ7
,
Inner grooved
Coil Length x Height x Width
mm
973×1320×38.1
973×1320×38.1
Heat Exchanging Area
m2
47.62
47.62
Air Flow Volume
CFM
3765
3765
m
3
/h
6400
6400
Noise Level
dB(A)
60
60
Dimension
(W×D×H)
Net
mm
940×368×1366
940×368×1366
Packing
mm
1080×460×1500
1080×460×1500
Weight
Net
kg
101
102
Gross
kg
112
113
Refrigerant
Type/Quantity
Type
R410A
R410A
Charged Volume
g
2750
2900
Design Pressure
MPa
4.4
4.4
Refrigerant
Piping
Liquid Side
mm
9.52
9.52
Gas Side
mm
19.05
19.05
Max. Length
m
50
50
Max. Height
m
30
30
Setting Temperature Range
°C
16~32
16~32
Operation
Temperature Range
Cooling
°C
-15~49
-15~49
Heating
°C
-15~24
-15~24
Application Area
m
2
56-93
64-107
Connection
Wiring
Power Wiring(Indoor)
mm
2
3×1mm
2
3×1mm
2
Power Wiring(Outdoor)
mm
2
5×4mm
2
5×4mm
2
Signal Wiring
mm
2
2×1mm
2
2×1mm
2
Stuffing
Quantity
20/40/40H
Unit
27/55/55
27/55/55
Notes:
1. Nominal cooling capacities are based on the following conditions: Return air temp.: 27°CDB, 19°CWB,
and outdoor temp.: 35°CDB, 24°CWB;
2. Nominal heating capacities are based on the following conditions: Return air temp.: 20°CDB, and
outdoor temp.: 7°CDB, 6°CWB;
3. Parameters above are all measured when the connecting pipe is 5 meters.
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...