AUX-Light CAC 50Hz R410A
Trouble shooting
124
5.Electric components malfunction inspection
No
Component
name
Inspection methods
1
Compressor
Using multi-meter ohm phase, there is correct resistance value among windings (single
phase compressor refers to specification, three phase compressor resistance
approximately equal), resistance of winding should be infinite.
2
Control board
1. 1Check if any connection part of PCB loosen or drop off, printed tinsel and
components have any burn, fade, breaking off or aging phenomenon, all joints exist
short circuit phenomenon etc.
2. Test the circuit board system in the term of voltage, pulse on, resistance variation,
by using testing meter.
3. Judge the output and input is normal or not according to electric principle diagram
3
Contactor
4.
Press the contactor by hand, the contactor reacts immediately and without
question
5.
The contacting point of contactor has no burn and melt phenomenon
6.
The winding has resistance value below 1000, but cannot be nil or infinite
4
4-ways valve
winding
The winding has resistance value below 1000, but cannot be nil or infinite
5
Capacitor
7.
No expansion phenomenon apparently
8.
Measure capacitor by using capacitor phase of multi-meter( if the multi-meter has
no capacitor phase, use ohm phase, contact the two terminal of meter to two feet of
capacitor, and quickly switch positive pole and negative pole and reconnect, the
resistance should display from nil to infinite quickly. The resistance can’t change is
always nil or infinite).
6
Sensor
9.
Using multi-meter to measure resistance, find out temperature according to
resistance table, the temperature should accord with sensor temperature.
10. Resistance cannot be nil or infinite
7
Motor
11. No burning trace apparently
12. Using multi-meter ohm phase, there is correct resistance value among windings
(single phase compressor refers to specification, three phase compressor resistance
approximately equal), resistance of winding should be infinite.
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...