AUX-Light CAC 50Hz R410A
Trouble shooting
106
Piping connection
◇
Using expanding machine to expand accessories, the size of horn shown in the above figure:
◇
Paint a thin layer of frozen oil at both inside and outside part of the expanding.
◇
Make the expanding right to the screw thread shape connection of the indoor unit, using hands to
tighten the nut then using a wrench to tighten the nut again, the tighten torque as follows figure.
◇
Take out the cover of the indoor unit gas valve and liquid valve, make the expanding right to the stop
valve of outdoor unit, using hands to tighten the nut then using a wrench to tighten the nut again, the
tighten torque as follows figure.
Equivalent pipe length conversion
Equivalent pipe length meansconverting pipe elbow to straight pipe length after considerate the pressure
loss.
Elbow and Oil loop conversion tablet
Pipe Dia.(mm)
Bend
Oil Loop
6.35
0.10
0.7
9.52
0.18
1.3
12.70
0.20
1.5
15.88
0.25
2.0
19.05
0.35
2.4
22.02
0.40
3.0
Equivalent pipe length L
=
ActualPipe length L+ Bend Qty× Equivalent pipe bend Oil Loop Qty ×
Equivalent Oil Loop length
Sample:
ALCA-H42A
5/C5 Actual Pipe length is 25 meters, Gas pipe diameter is 19.05mm. If there’s 5 bends and 2
oil loops during the installation, then the equivalent pipe length should be:
L=25+0.35×5+2.4×2=31.5(m)
◇
Specification of connection pipe for indoor unit and outdoor unit
Cooling Capacity(Btu/h)
12000
18000
24000
36000
48000
60000
Connection
Pipe (mm)
Liquid Pipe
Φ6.35
Φ9.52
Φ9.52
Gas Pipe
Φ12.7
Φ15.88
Φ19.05
Max. Length
15
20
30
50
50
Max. Height (m)
10
15
15
30
30
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...