AUX-Light CAC 50Hz R410A
Trouble shooting
112
7.3.2 Electrical connection
Wiring diagram of indoor & outdoor, refer to the section of part 1
Recommendation of power supply cord
Power supply:220V-240V~,50Hz
Cooling capacity
(Btu/h)
Model
Power supply
spec.
Power supply
side
Power supply
cord
Connection wires
12000
ALCA-H12/4R1AA
ALCF-H12/4R1C
ALMD-H12/4R1D
220-240V~50Hz
Indoor side
3×2.5mm
2
3×2.5mm
2+
2x1 mm
2
18000
ALCA-H18/4R1AA
ALCF-H18/4R1C
ALMD-H18/4R1D
220-240V~50Hz
Indoor side
3×2.5mm
2
3×2.5mm
2+
2x1 mm
2
24000
ALCA-H24/4R1AA
ALCF-H24/4R1C
ALMD-H 24/4R1D
220-240V~50Hz
Outdoor side
3×6mm
2
3x2.5mm
2+
3×1mm
2
36000
ALCA-H36/4R1E
ALCF-H36/4R1
ALMD-H 36/4R1
220-240V~50Hz
Outdoor side
5×4mm
2
3x4 mm
2+
2×1mm
2
Power supply 380V-415V~,3N,50Hz
Cooling capacity
(Btu/h)
Model No.
Power supply
spec.
Power supply cord
of indoor unit
Power supply cord
of outdoor unit
Connection
wires
36000
ALCA-H36/5R1AA
ALCF-H36/5R1C
ALMD-H36/5R1D
Outdoor unit
380-415V
3N~50Hz
Indoor unit
220-240V~50Hz
Indoor and
outdoor input
separately
3×1 mm
2
5×4mm
2
2×1 mm
2
48000
ALCA-H48/5R1AA
ALCF-H48/5R1C
ALMD-H48/5R1D
60000
ALCA-H60/5R1AA
ALCF-H60/5R1C
ALMD-H60/5R1D
Notice:
◇
Above mentioned power supply cord is the cable which connect air on-off of indoor to indoor/outdoor
unit. Power supply cord of indoor/outdoor unit is the power supply cable connecting indoor and outdoor
unit
◇
The section area of power supply cord core is minimized one. To avoid voltage pressure dropped down,
while longer power supply cord needed, the section area should be enlarged for one gauge.
◇
The connection wires to indoor unit is the cable of 27IEC53(RVV) type, 300/500V; while the connection
wires to outdoor unit and the connection wires from outdoor to indoor unit is the multi-end of cable
(neoprene)of 245IEC57(YZW)type,300/500V. if the single core with double skin type of cable is chosen
for installation,, please choose 1# gauge of section area and wrapped with special jacket for
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...