AUX-Light CAC 50Hz R410A
Trouble shooting
111
7.3. Electrical connection
7.3.1Electrical connection precaution
Warning
Installation of electric items must be carried out by qualified, professional technicians. An isolated circuitry
should be fixed with whole-pole disconnection devices, which is with at least 3mm gap of touch point. .
Power supply and indoor to outdoor connection should use special cable. Providing the necessity of
installation or replacement, the professional technician of service store appointed by manufacturer must
be required, while self-operation by users is prohibited.
In case of any electric shock accident, the creepage protection devices /power supply on-off and breaker
must be required with power supply.
The specification of fuse for single phase control board is F5AL 250V, while for 3 phase control board,
both indoor and outdoor unit, it is F3.15AL 250V
。
Machine must be earthed surely. If not, it’ll be probably caused creepage.
Equivalent 227IEC53(RVV) type of power cord of GB5023 or the excelled must be required. The cords
should be fixed properly against broken, while ends/joints of cords is under outside force. Improper
connection or fixation will cause disaster like fire….etc. Equivalent 245IEC57(YZW) type of power cord of
GB5023 or the excelled must be used as connection line of indoor and outdoor.
Notice
The earth line is neither allowed to connect to gas pipe, water pipe or circuitry of telephone or lighting rod,
nor to the earth line of other devices.
Others
Please fix power supply cord and connection wires of indoor and outdoor, in accordance with circuit
diagram
Fix the cords into terminal boards properly and safely with cable fixation tools to avoid any danger caused
by the power cord under outside forces.
After fixation, use bind tape (affixed) to bind wires avoiding any collision with other components like
compressor, copper pipes…etc
Summary of Contents for AL-H12/4R1D
Page 4: ...AUX Light Commercial Air Conditioners T1 50Hz R410a ON OFF 4 1 Nomenclature ...
Page 72: ...AUX Light CAC 50Hz R410A Universal outdoor unit 72 ALMD H18 4R1D ALMD H24 4R1D ...
Page 93: ...AUX Light CAC 50Hz R410A Trouble shooting 93 1366 610 160 438 368 388 940 ...
Page 129: ...AUX Light CAC 50Hz R410A Trouble shooting 129 Outdoor protection phase sequence ...
Page 130: ...AUX Light CAC 50Hz R410A Trouble shooting 130 Cooling high pressure protection ...
Page 131: ...AUX Light CAC 50Hz R410A Trouble shooting 131 Heating high pressure protection ...
Page 132: ...AUX Light CAC 50Hz R410A Trouble shooting 132 Cooling low pressure protection ...
Page 133: ...AUX Light CAC 50Hz R410A Trouble shooting 133 Heating low pressure protection ...
Page 134: ...AUX Light CAC 50Hz R410A Trouble shooting 134 Cooling exhaust temperature protection ...
Page 135: ...AUX Light CAC 50Hz R410A Trouble shooting 135 Heating exhaust temperature protection ...
Page 137: ...AUX Light CAC 50Hz R410A Trouble shooting 137 Sensor failure protection ...
Page 138: ...AUX Light CAC 50Hz R410A Trouble shooting 138 No action after power on ...
Page 139: ...AUX Light CAC 50Hz R410A Trouble shooting 139 Poor effect ...
Page 140: ...AUX Light CAC 50Hz R410A Trouble shooting 140 ...
Page 141: ...AUX Light CAC 50Hz R410A Trouble shooting 141 Abnormal sound or viberation ...
Page 142: ...AUX Light CAC 50Hz R410A Trouble shooting 142 ...
Page 143: ...AUX Light CAC 50Hz R410A Trouble shooting 143 Abnormal odor ...
Page 145: ...AUX Light CAC 50Hz R410A Trouble shooting 145 Air conditioner water leakage ...