The AADvance Safety Controller
[13]
Schedule
[14]
TYPE EXAMINATION CERTIFICATE No.
DEMKO 11 ATEX 1129711X
Rev. 3
Report: 4786831849
00-IC-F0060
–
Issue 9.0
This certificate may only be reproduced in its entirety and without any change, schedule included.
Page
3
of
3
Voltage(Vdc)
Current (mA)
9831
18-32
0-24
-
9832
18-32
0-24
-
9833
0-32
6.5
-
9851
18-32
500
-
9852
18-32
500
-
9892
18-32
500
-
9881
18-32
0-24
-
9882
18-32
0-24
-
Routine tests
None
[16]
Descriptive Documents
The scheduled drawings are listed in the report no. provided under item no. [ 8 ] on page 1 of this Type Examination Certificate.
[17]
Special conditions for safe use:
x
Models 9110 and 9111: The ambient temperature range is -25
q
C to +60
q
C.
x
All other Models: The ambient temperature range is -25
q
C to +70
q
C.
x
Devices are to be installed in an ATEX Certified, IP54, tool accessible enclosure that has been evaluated to the requirements of EN
60079-0: 2012+A11:2013 and EN 60079-15: 2010. Enclosure is to be marked with the following: "Warning - Do not open when
energized". After installation of subject devices into the enclosure, access to termination compartments shall be dimensioned so that
conductors can be readily connected. Grounding conductor should have a minimum cross sectional area of 3.31 mm
2
.
x
Devices are for use in an area of not more than pollution degree 2 in accordance with IEC 60664-1.
x
Devices are to use conductors with a minimum conductor temperature rating of 85°C.
x
Devices are to be installed in the vertical orientation only.
[18]
Essential Health and Safety Requirements
Met by compliance with the standards EN 60079-0:2012+A11:2013, EN 60079-15:2010.