60
Rockwell Automation Publication ICSTT-RM448J-EN-P - April 2018
Chapter 2
The AADvance Safety Controller
• IP addresses have been configured for the processor modules – use the
AADvance Discover tool installed with the Workbench
• The 9110 processor modules have been rebooted in Recovery Mode, if
the modules are rebooted into Recovery Mode at the same time a single
ControlFLASH update will be applied to all the modules
Update procedure:
• Run the ControlFLASH program
• Select the type of module from the list
• Browse to the T9110 Processor Module
• Select the version of the firmware to be installed (NOTE: it may be
necessary to tick the “Show all versions” checkbox to see the version
required)
• Update the module
• The firmware will be downloaded and stored on the module – this will
take approximately 5 minutes
• The modules will be rebooted to confirm the firmware has been updated
successfully
Refer to document
1756-UM105 ControlFLASH firmware Upgrade Kit User
Manual
in the Literature Library for detailed instructions for using
ControlFLASH.
.
Ethernet Communication Protocols
AADvance Ethernet ports are used to support several transport layer services;
these services are listed in the following table:
NOTE
When updating the firmware, it is recommended that RSWho
is not actively browsing the 9110 Processor module.
Protocol
Port Number
Purpose
TCP
502
MODBUS Slave
TCP
1132
ISaGRAF, application downloads, debug, SoE
TCP
10001-10006
Transparent Communication Interface (Serial Tunnelling)
TCP
4818
CIP Produce & Consume
TCP
N/A
Telnet (diagnostic Interface)
UDP
1123,1124
IXL Bindings
UDP
2010
Discovery and configuration Protocol