Rockwell Automation Publication ICSTT-RM448J-EN-P - April 2018
55
The AADvance Safety Controller
Chapter 2
Backplane Electrical Ratings
To comply with UL/CSA standards use the following voltage and current
ratings for the Processor and I/O Backplanes when designing your power
distribution:
Table 5 - Maximum Electrical Rating Values
IMPORTANT
These are the maximum allowed electrical ratings given by UL for the
backplane load installed with the relevant TAs and modules. They are not
operating values so don't use them to calculate the controller power
consumption or heat dissipation values. Refer to the separate topics on
estimating Heat Dissipation and Power Consumption.
Module
Back-plane Electrical Ratings
Input/Output Electrical Ratings
Voltage Range (Vdc)
Maximum Current (mA)
9100
18-32
10.4A (400 mA per slot)
-
9300
18-32
9.6A (400 mA per slot)
-
9110
18-32
380
-
9401
18-32
260
Input: 18-32 Vdc @ 24 mA
9402
18-32
260
Input: 0-32 Vdc @ 6.5 mA
9431
18-32
260
Input: 0-32 Vdc @ 6.5 mA
9432
18-32
260
Input: 18-32 Vdc @ 24 mA
9481
18-32
260
Output: 18-32 Vdc/0-20 mA
9482
18-32
260
Output: 18-32 Vdc/0-20 mA
9451
18-32
165
Output: 18-32 Vdc @ 0.5 A, Pilot duty 16 VA,
1.5 A Inrush
9801
18-32
6.5
-
9802
18-32
6.5
-
9803
18-32
6.5
-
9831
18-32
0-24
-
9832
18-32
0-24
-
9833
18-32
0-24
-
9851
18-32
500
-
9852
18-32
500
-
9892
18-32
500
-
9881
18-32
0-24
-
9882
18-32
0-24
-