114
Rockwell Automation Publication ICSTT-RM448J-EN-P - April 2018
Chapter 5
Install the AADvance System
Figure 20 - Digital Output Field Circuit
Recommended Fuse Types
The 10A fuses are fitted into the termination assembly and are:
• T9902: SMF Omni-Block, Surface Mount Fuse Block 154 010, with a
10A, 125V Fast Acting Fuse, Littelfuse.
WARNING:
For inductive loads, a back EMF protection diode shall be fitted at
the load.
WARNING:
A fuse rated minimum 32 Vdc, maximum 5 A for an input of 0 -
28.3 V and a maximum fuse current rating of 100 V for an input of 28.3 - 42.4
V must be installed in series with the field power terminals on modules
T9451 to comply with the UL 508 certification.