138
Rockwell Automation Publication ICSTT-RM448J-EN-P - April 2018
Chapter 6
System Start-Up
Procedure for Installation of a Second and Third Processor
The second and third processor modules must have the same firmware version
as the first processor. If the firmware revision is different upgrade the firmware
using the ControlFLASH utility.
Table 13 - Procedure for Installation of a Second and Third Processor
IMPORTANT
When inserting a second and third processor module they MUST be inserted
one at a time and allowed to educate before inserting the next one.
Step
Task
1.
Place the processor module on slot B on the Processor Base Unit connectors and push the module home
until the connectors are fully mated. Turn the locking screw with a flat bladed screwdriver and lock the
module in position.
All the Module LEDs are OFF until the module is installed. As soon as the module receives power it will
boot up then educate and show the following indications:
Healthy
Flashes RED for a second then goes GREEN as the module boots up (10 to 20 seconds)
Ready
Will stay OFF as the module boots up (10 to -20 seconds) then goes RED for 10
seconds then flashes GREEN as it educates and lastly it goes to steady GREEN
Run
Will stay OFF as the module boots up (10 to 20 seconds) then goes RED until
educated and then it goes AMBER
System Healthy
Will stay OFF as the Module boots up (10 to 20 seconds) then goes GREEN
Force
Will stay OFF as the Module boots up (10 to 20 seconds) then stays OFF until the
module has educated and the application is running
Aux
Will stay OFF as the Module boots up (10 to 20 seconds) then is depends on data
connection
Serial 1
Will stay OFF as the Module boots up (10 to 20 seconds) then is depends on data
connection
Serial 2
Will stay OFF as the Module boots up (10 to 20 seconds) then is depends on data
connection
Ethernet 1
Will stay OFF as the Module boots up (10 to 20 seconds) then is depends on data
connection
Ethernet 2
Will stay OFF as the Module boots up (10 to 20 seconds) then is depends on data
connection
When the Run indicator goes AMBER push the Fault Reset button and the processor will show the following
indications:
2.
Healthy
GREEN
Ready
GREEN (will flash for a short time as the module educates)
Run
AMBER to GREEN (AMBER as the module educates)
System Healthy
GREEN
Force
Off to GREEN
Aux
Depends on application
Serial 1
Depends on data Connection
Serial 2
Depends on data Connection
Ethernet 1
Depends on data Connection
3.
To insert a 3rd processor module repeat step 1 and insert in slot C.