80
Rockwell Automation Publication ICSTT-RM448J-EN-P - April 2018
Chapter 4
Before You Begin
Table 8 - Field Loop Power Heat Dissipation
The field loop power heat dissipation is generated from the input voltages and
cu the output currents:
1
The maximum field loop power heat dissipation for analogue outputs should
be calculated at an output current corresponding to the smaller of the
Maximum Channel Output Current OR Field Voltage/(2 x Load Resistance)
Estimate AADvance
Controller Weight
Use the following table to make an estimate of the weight of your controller.
Table 9 - AADvance Controller Module Weight
Item
Number of
Field Loops
Field Loop Power
Heat Dissipation
Subtotal
(W x 3.412 BTU/hr)
Digital Inputs
× Input Voltage (V)/5125
=
Analogue Inputs
× Input current (A) x 135
=
Digital Outputs
x Output current (A) x 0.57
=
Analogue outputs
x (Field voltage(V) x Output
Current (A) - load Resistance (
)
x Output current (A)
1
=
Total:
Item
Number
Used
Weight Allowance g
(oz.)
Subtotal
T9100 Processor Base Unit
× 460 g (16 oz.)
T9110 Processor Module
× 430 g (15 oz.)
T9401 Digital input module, 24 Vdc, 8 channel
× 280 g (10 oz.)
T9402 Digital input module, 24 Vdc, 16 channel
× 340 g (12 oz.)
T9431 Analogue input module, 8 channel
× 280 g (10 oz.)
T9432 Analogue input module, 16 channel
× 340 g (12 oz.)
T9451 Digital output module, 24 Vdc, 8 channel
× 340 g (12 oz.)
T9482 Analogue output module, 8 channel
× 290 g (10.5 oz.)
T9300 I/O base unit (3 way)
× 133 g (5 oz.)
T98x1 Simplex Termination assembly
× 133 g (5 oz.)
T98x2 Dual Termination Assembly
× 260 g (10 oz.)
T98x3 Triple Termination Assembly
× 360 g (13 oz.)
T9310 Expansion cable assembly and 2 m cable
× 670 g (24 oz.)
T9841 Termination Assemblies (average weight)
× 175 g (6 oz.)
Total estimated controller weight