The AADvance Safety Controller
Chapter 2
Table 3 - Environmental Specification
1
There is no specific protection against liquids.
Attributes
Value
Operating Temperature Range:
For use in Hazardous Environments:
Processor Modules
I/O Modules and Termination Assemblies
For use in Non-hazardous Environments:
Processor Modules, I/O modules and Termination
Assemblies
–25 °C to +60 °C (–13 °F to +140 °F)
–25 °C to +70 °C (–13 °F to +158 °F)
–25 °C to +70 °C (–13 °F to +158 °F)
Storage and Transport Temperature Range
–40 °C to +70 °C (–40 °F to +158 °F)
Module Surface Temperature (during usual operation)
43° C (109 °F) ± 2 °C
Humidity
Operating
10 % to 95 % RH, non-condensing
Storage and Transport
10 % to 95 % RH, non-condensing
Vibration
Functional Stress
5 Hz to 9 Hz
Continuous
1.7 mm amplitude
Occasional
3.5 mm amplitude
Withstand
10 Hz to 150 Hz
Acceleration
0.1 g in 3 axes
Endurance
10 Hz to 150 Hz
Acceleration
0.5 g in 3 axes
Shock
15 g peak, 11 ms duration, ½ sine
Altitude
Operating
0 to 2,000 m (0 to 6,600 ft.)
Storage and Transport
0 to 3,000 m (0 to 10,000 ft.)
This equipment must not be transported in
unpressurized aircraft flown above 10,000 ft.
Electromagnetic Interference
Tested to the following standards: EN 61326-1:2006,
Class A; EN 61326-3-1:2008, EN 54-4: 1997, A1; EN
61131-2:2007; EN 62061:2005.
Hazardous Location Capability
Suitable for Class I Div 2 Groups A, B, C and D