5-1
C H A P T E R 5
Sensor Installation and
Connection
The ADS
®
flow monitor and sensors are primarily
designed for monitoring flow in sanitary, storm, and combined
sewers. The monitor mounts to the manhole rim or wall slightly
below the manhole cover or to a rung in the manhole.
A sewer system’s hydraulics are much
more stable and uniform in
the incoming pipe than in the manhole invert or outgoing pipe.
Therefore, the sensors mount to a stainless steel expandable ring or
stainless steel bands installed in the sewer pipe a short distance
upstream from the manhole invert. Installing the sensors upstream
minimizes the hydraulic effects and erroneous data readings caused
by foamy waters, waves in the flow, sewer noise, non-laminar flow,
and obstructions in the manhole.
Following is the basic procedure for installing the
monitor and sensors at a location:
z
Investigate the Site Characteristics
These characteristics
include pipe size and shape, silt level, flow depth, and
hydraulic conditions.
z
Prepare the Equipment for Installation
The monitor,
communication system, and sensors must be prepared and
initialized for installation (
See Chapters 3 and 4 for
communication and initial monitor setup)
.
Summary of Contents for 507165
Page 20: ...1 12 ADS TRITON Manual Control Drawing ...
Page 27: ...Introduction 1 19 CS6 LRD Sensor Certificate of Conformity ...
Page 29: ...Introduction 1 21 CSA Certificate of Compliance Page 1 of 7 ...
Page 30: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 2 of 7 ...
Page 31: ...Introduction 1 23 CSA Certificate of Compliance Page 3 of 7 ...
Page 32: ...1 24 ADS TRITON Manual CSA Certificate of Compliance Page 4 of 7 ...
Page 33: ...Introduction 1 25 CSA Certificate of Compliance Page 5 of 7 ...
Page 34: ...1 26 ADS TRITON Manual CSA Certificate of Compliance Page 6 of 7 ...
Page 35: ...Introduction 1 27 CSA Certificate of Compliance Page 7 of 7 ...
Page 37: ...Introduction 1 29 Sample TRITON Declaration of Conformity Page 2 ...
Page 53: ...System Overview 2 13 ExPAC XBUS ...
Page 266: ...5 60 ADS TRITON Manual z Installing the Submersion Sensor z Measuring the physical offset ...
Page 288: ...5 82 ADS TRITON Manual Topside Wall Mount Bracket Topside Sensor Bracket ...
Page 345: ...7 2 ADS TRITON Manual use of this installation guide or the installation of any ADS equipment ...
Page 358: ...Inclinometer 8 3 ...
Page 507: ...C 4 ADS TRITON Manual ...
Page 535: ...Index In 19 wiring to the monitor 6 29 XIO device parameters 4 84 ...