Configuration and Activation 4-67
Surcharge Detection
Select the Disable checkbox to
prevent the monitor from implementing the Surcharge
Detection function when processing Smart Depth data.
For locations that typically do not experience surcharge,
disabling Surcharge Detection eliminates the processing
time required for this function and, as a result, conserves
monitor power.
Sensor
z
Physical Offset
Enter the physical distance from the face of the
sensor to the crown (top) of the pipe.
Refer to Chapter 5, Sensor
Installation and Connection, for instructions on measuring the physical
offset.
z
Pipe Height
This field displays the pipe height at the monitor
location, based on the installation table.
This parameter is not editable
from this location.
z
Channel
Select the channel number of the port on top of the monitor
to which this device is connected.
Temperature
The temperature sensor measures the air temperature in the pipe to
apply when calculating the speed of sound in air.
Note:
Under normal conditions, the parameters in the
Temperature
section should not require modification.
However, if additional adjustments are necessary, refer to
the detailed description of each parameter.
z
Sensor
Select the source from which to measure the
temperature used when compensating for temperature in
Ultrasonic Depth Sensor readings. The channels correspond to
the sensors connected to those channels (i.e., ports) on the
monitor. The option selected here should be consistent with
the option selected for the
Channel
in the
Sensor
section to the
left of the
Temperature
section.
Note:
The
stored
temperature value is the actual air
temperature reading from the Ultrasonic Depth Sensor.
Summary of Contents for 507165
Page 20: ...1 12 ADS TRITON Manual Control Drawing ...
Page 27: ...Introduction 1 19 CS6 LRD Sensor Certificate of Conformity ...
Page 29: ...Introduction 1 21 CSA Certificate of Compliance Page 1 of 7 ...
Page 30: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 2 of 7 ...
Page 31: ...Introduction 1 23 CSA Certificate of Compliance Page 3 of 7 ...
Page 32: ...1 24 ADS TRITON Manual CSA Certificate of Compliance Page 4 of 7 ...
Page 33: ...Introduction 1 25 CSA Certificate of Compliance Page 5 of 7 ...
Page 34: ...1 26 ADS TRITON Manual CSA Certificate of Compliance Page 6 of 7 ...
Page 35: ...Introduction 1 27 CSA Certificate of Compliance Page 7 of 7 ...
Page 37: ...Introduction 1 29 Sample TRITON Declaration of Conformity Page 2 ...
Page 53: ...System Overview 2 13 ExPAC XBUS ...
Page 266: ...5 60 ADS TRITON Manual z Installing the Submersion Sensor z Measuring the physical offset ...
Page 288: ...5 82 ADS TRITON Manual Topside Wall Mount Bracket Topside Sensor Bracket ...
Page 345: ...7 2 ADS TRITON Manual use of this installation guide or the installation of any ADS equipment ...
Page 358: ...Inclinometer 8 3 ...
Page 507: ...C 4 ADS TRITON Manual ...
Page 535: ...Index In 19 wiring to the monitor 6 29 XIO device parameters 4 84 ...