Configuration and Activation 4-65
However, if additional adjustments are necessary, refer to
the detailed description of each parameter.
z
Electronic Offset
Enter the difference that exists between
the smart depth sensor readings and the manually measured
depth, when applicable.
The default value is 0.
Note:
An electronic offset is rarely needed. An offset
greater than +/- 0.5 inches (13 mm) typically indicates that
the physical offset or pipe height has been measured or
recorded incorrectly.
z
Mode
Select the mode in which you want the smart depth
sensor to operate based on environmental factors or site
constraints. The default setting is
Normal
power. However, if
erratic
Smart Depth
readings occur, consider changing the
Power
setting to
High
power.
z
Blanking
Select the distance from the horizontal face of the
ultrasonic depth sensor within which to ignore data potentially
representing erroneous readings. Select the
Auto
option
(
default
) to ensure the monitor disregards depths occurring
within a distance from the horizontal face of the sensor
equivalent to 5 percent of the range from the sensor face to the
bottom of the pipe. This option represents most pipe/flow
conditions; therefore, ADS strongly recommends leaving this
option selected for most applications.
Choose one of the other
options only when spikes in the data are occurring beyond 5
percent of this range and under direct consultation with an
ADS representative.
z
Store Data
Select this checkbox to ensure the monitor logs
the smart depth data to memory.
This option is selected by
default.
z
Advanced
Select this button to access the
Advanced
Parameters
dialog.
Summary of Contents for 507165
Page 20: ...1 12 ADS TRITON Manual Control Drawing ...
Page 27: ...Introduction 1 19 CS6 LRD Sensor Certificate of Conformity ...
Page 29: ...Introduction 1 21 CSA Certificate of Compliance Page 1 of 7 ...
Page 30: ...1 22 ADS TRITON Manual CSA Certificate of Compliance Page 2 of 7 ...
Page 31: ...Introduction 1 23 CSA Certificate of Compliance Page 3 of 7 ...
Page 32: ...1 24 ADS TRITON Manual CSA Certificate of Compliance Page 4 of 7 ...
Page 33: ...Introduction 1 25 CSA Certificate of Compliance Page 5 of 7 ...
Page 34: ...1 26 ADS TRITON Manual CSA Certificate of Compliance Page 6 of 7 ...
Page 35: ...Introduction 1 27 CSA Certificate of Compliance Page 7 of 7 ...
Page 37: ...Introduction 1 29 Sample TRITON Declaration of Conformity Page 2 ...
Page 53: ...System Overview 2 13 ExPAC XBUS ...
Page 266: ...5 60 ADS TRITON Manual z Installing the Submersion Sensor z Measuring the physical offset ...
Page 288: ...5 82 ADS TRITON Manual Topside Wall Mount Bracket Topside Sensor Bracket ...
Page 345: ...7 2 ADS TRITON Manual use of this installation guide or the installation of any ADS equipment ...
Page 358: ...Inclinometer 8 3 ...
Page 507: ...C 4 ADS TRITON Manual ...
Page 535: ...Index In 19 wiring to the monitor 6 29 XIO device parameters 4 84 ...