KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA00xx73xxxxx
│
238
10.24.75 Setpoint adjustment — Resetting the manual adjustment via object
Options:
Deactivated
Activated
If this parameter is activated, a separate object can be used to delete the manual adjustment at
any time. Example of application: Resetting the manual adjustment on all devices located in an
office building using a system clock.
10.24.76 Setpoint adjustment — Permanent storage of on-site operation
Options:
Deactivated
Activated
If this parameter is activated, the manual settings for setpoint and, where applicable, fan speed
level, as well as the value of the "Basic load" object, will be stored in the device and re-activated
after a reset. The same applies to the operating mode.
If the device is re-programmed, the stored setpoint values will also be deleted.
10.24.77 Setpoint adjustment — Permanent storage of on-site operation
Options:
Deactivated
Activated
If this parameter is activated, the manual settings for setpoint and, where applicable, fan speed
level, as well as the value of the "Basic load" object, will be stored in the device and re-activated
after a reset. The same applies to the operating mode.
If the device is re-programmed, the stored setpoint values will also be deleted.
10.24.78 Temperature reading — Inputs of temperature reading
Options:
Internal measurement
External measurement
Weighted measurement
The room temperature can be measured at the device or fed to the device by an object via the
bus. In addition, weighted measuring is also available, in which the weighted average of up to
three temperature values (1 x internal, 2 x external) is calculated and used as an input value for
control.