KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA00xx73xxxxx
│
213
10.24.4 General — Send cyclic "In operation" (min)
Options:
Setting option between 5 - 3000 minutes
– Communication object "In operation" serves for the information that the controller still
operates. Value "1" is sent cyclic. The cycle for sending is set via this parameter. If there is
no cyclic telegram, the function of the device is disturbed and the air-conditioning of the
room can be maintained via forced control. For this, however, the system and/or actuator
must have the "Forced control" function.
10.24.5 General - Additional functions/objects
Options:
Deactivated
Activated
– This parameter enables additional functions and communication objects.
10.24.6 General — Delay time for read telegrams after reset [s]
Options:
Setting option from 1 - 255 seconds
– This parameter can be used to receive telegrams via the "Input" object. The received
telegrams are sent with the set delay time to the "Output" object after a reset.
Note
This parameter is only available if the "Additional function" parameter is set to
"Yes".